Maximize installation and application flexibility with the coplanar platform
■ Improve reliability and performance with integrated DP Flow meters, DP Level solutions, and integral manifolds.
■ Easy installation with all solutions fully assembled, leak-tested, and calibrated.
■ Meet your application needs with an unsurpassed offering.
Proven best-in-class performance, reliability, and safety
■ More than seven million installed
■ Reference accuracy 0.04 percent of span
■ Installed total performance of 0.14 percent of span
■ 10-year stability of 0.2 percent of URL
■ SIL2/3 certified (IEC 61508)
■ Rosemount Coplanar™plat formenables integration of primary elements,manifolds,and remoteseal solutions
■ Best in Class performance with up to 0.05% high accuracy option
■ IEC 62591(WirelessHART®)Protocol enables cost effective installations
■ Local Operator Interface (LOI) offers easy to use configuration capabilities at the transmitter
■ Protocols available include HART®4–20mA,FOUNDATION™Fieldbus,PROFIBUS®PA,HART1–5VdcLow Power
■ Selectable HART Revision prepares your plant for the latest HART capabilities while ensuring seamless integration with today's systems
■ SIL2/3safety certification to IEC61508 is available with the full 4–20mA HART offering to simplify compliance
This product data sheet covers HART, Wireless, FOUNDATION Fieldbus, and PROFIBUS PA Protocolsunless specified.
Conformance to specification (±3s[sigma])
Technology leadership, advanced manufacturingtechniques, and statistical process control ensure specification conformance toat least ±3s.
Reference accuracy
Stated reference accuracy equations include terminal based linearity, hysteresis, and repeatability. For Wireless,FOUNDATION Fieldbus, and PROFIBUS PA devices, use calibrated range in place of span.
Models | Standard | High performance option, P8 | |
Rosemount 2051C | |||
Range 1 | ±0.10% of span For spans less than 15:1, accuracy = ±æ0.025+0.005 --U----R---L---ö %ofspan è Spanø |
N/A |
N/A |
Ranges 2–4 |
±0.065% of span For spans less than 10:1, accuracy = ±æ0.025+0.005 --U----R---L---ö %ofspan è Spanø |
Ranges 2–4 | High accuracy option, P8 ±0.05% of span For spans less than 10:1(1), accuracy = ±æ0.015+0.005 --U-----R---L--- ö %ofspan è Spanø |
Range 5 |
±0.075% of span For spans less than 10:1, accuracy= ±æ0.025+0.005 --U-----R---L--- ö %ofspan è Spanø |
Range 5 | High performance option, P8 ±0.065% of span For spans less than 10:1, accuracy= ±æ0.015+0.005 --U----R---L---- ö %ofspan è Spanø |
Rosemount 2051T, 2051G | |||
Ranges 1–4 |
±0.065% of span For spans less than 10:1, accuracy = ±æ0.0075 --U----R---L---ö %ofspan è Spanø |
Ranges 1–4 | High accuracy option, P8 ±0.05% of span For spans less than 10:1(1), accuracy = ±æ0.0075 --U----R---L---- ö %ofspan è Spanø |
Range 5(2) | ±0.075% of span For spans less than 10:1, accuracy = ±æ0.0075 --U----R---L---ö %ofspan è Spanø |
N/A |
N/A |
Rosemount 2051L | |||
Ranges 2–4 | ±0.075% of span For spans less than 10:1, accuracy = ±æ0.025+0.005 --U-----R---L--- ö %ofspan è Spanø |
N/A |
N/A |
1. For protocol code F, accuracy specification is for spans less than 7:1. Not available with out put codeW.
2. Rosemount 2051G is not available with Range5.
We, Tianjin Seles Electromechanical Technology Co., LTD, are a high-tech enterprise located in Tianjin Binhai New Area. We are supplier, distributor, wholesaler & trader of Emerson Mass Flowmeter. Products model included in this range are CMF010,CMF025,CMF050,CMF100,CMF200,CMF300,CMF400; F025,F050,F100,F200,F300,F400.